   Mobile:86-13611976994
  E-mail:Grace@acrel.cn
Home » Products » Energy Meter » DC Energy Meter » Energy meter 24 48 circuits AMC series
Share to:

Energy meter 24 48 circuits AMC series

  • multi circuits max 96 branches
  • 0.5 class
  • Din Rail / Wall Mounted
  • AC / DC
 
RoHS IEC
Quantity:

Energy meter 24 48 circuits AMC series

With the rapid development of data centers,the energy consumption of data centers has become more and more prominent. Energy management and power supply and distribution design of data centers have become a hot issue. Efficient and reliable data center power distribution system is an effective way to improve the energy use efficiency of data centers and reduce equipment energy consumption.To realize energy saving of data center,it is necessary to monitor each electrical load first. However,there are many load loops in data center,and traditional measuring instruments cannot meet the requirements of cost,volume,installation,construction and other aspects. Therefore,multi-loop monitoring devices suitable for centralized monitoring of data center areneeded.

AMC16Z series DC precise distribution monitoring device is a measurement device designed specifically for data center server power management.The device design exquisite,can for A + B two into line and 96 road for electrical parameters,the input and output parameters of the switch state and the lightning protection device such as real-time monitoring,all alarm threshold measurement channels can be set in A separate,to qualify the limit event trigger system sound and light alarm,immediately on the volume in the traditional instrument,the height of the monitoring circuit integration.




Function description of Energy meter 24 48 circuits AMC series

Model

Function description

 

AMC16Z-ZD

Monitor the full-power parameters of the A+B double-channel DC feed circuit,6-way switch status monitoring,2-way alarm output,1-way temperature and humidity

detection,1-way RS485 communication,±12V output (only power supply to the feed circuit module supporting Hall sensor).

AMC16Z-FD

Monitor the full-power parameters of A+B double-channel DC outlet 24 and 1-channel RS485 communication.

AMC16Z-FDK24

Monitor the full-power parameters and switching status of A+B double-channel DC outlet 24 and 1-channel RS485 communication.

AMC16Z-FDK48

Monitor the full-power parameters and switching status of A+B double-channel DC off-line 48 sub-lines and 1-channel RS485 communication.

AMC16Z-KA

Wet contact,monitor A+B total 48 branch switch status,1 channel RS485 communication.

AMC16Z-KD

At the dry contact,the switch status of A+B consists of 48 branches and RS485 communication is monitored.

AMC16Z-DC48V

DC48V extended power supply,when the monitoring circuit exceeds A+B total 96 branches

AMC16Z-DC240/336V

DC240V/336V extended power supply,used when the monitoring circuit exceeds A+B total 96 branches




Dimension drawings of Energy meter 24 48 circuits AMC series


   



    




Typical connection of Energy meter 24 48 circuits AMC series


Technical parameter of Energy meter 24 48 circuits AMC series

DC incoming line

Technical parameters

AMC16Z-ZD

Measured parameters

Voltage,current,power,electric energy,ambient temperature and humidity

 

 

Bus voltage

Rated

48VDC,240VDC,336VDC

Measured range

±20%

Overload

Instantaneous voltage 2 times per second

Currentincoming line circuit

Rated

5V (Hall sensor,powered by AMC16Z-ZD ±12V)

Overload

Duration 1.2 times,instantaneous 10 times/second


 

Temperatue and humidity

Temperature range

-40℃-+99℃

Humidity range

20%-90%

 

Measurement precision

Incoming line

Voltage/current Class 0.5,power/electric energy Class 1

Temperature

±1℃

Humidity

±5%

Auxiliary power

Signal take electricity(≤15W)

 

Environment

Temperature

Work: -15℃ ~ 55℃ Storage: -25℃ ~ 70℃

Humidity

Relative humidity ≤93%

Altitude

≤2500m

Switching output

2 way 3A 250VAC /3A 30VDC

Switching input

6 way dry contact

Communication

RS485/Modbus-RTU

Installation

DIN35mm guide rail or baseplate mounted

Protection grade

IP20

Pollution levels

2

Security

Insulation

All terminals and the insulation resistance between the conductive pieces not

below 100 m Ω

 

Pressure

A circuit voltage and current signal // B circuit voltage and current signal // Switching output // other ports should meet AC2kV 1min between pairs,switching input and other ports should meet AC0.5kV 1min,leakage current

should be less than 2mA,no breakdown or flashering phenomenon.

 

 

Electro magnetic compatibility

Antistatic interference

Class 4

Resistance to rapid transient pulse groups

 

Class 3

Resistant to surge

interference

 

Class 4

Radio frequency

electromagnetic radiation

 

Class 3


DC outgoing line

Technical parameters

AMC16Z-FD

Measured parameter

Voltage,current,power,electric energy

 

Bus voltage

Ratetd

48VDC,240VDC,336VDC

Measured range

±20%

Overload

Instantaneous voltage 2 times per second

 

Currentoutcoming line circuit

Rated

 

5V (Hall sensor,external power supply ±12V)

Range

Overload

Duration 1.2 times,instantaneous 10 times/second

Measurement precision

Outgoing line

Voltage/current level 0.5,power/electric energy level 1

Auxiliary power

Get power from AMC16Z-ZD

 

Environment

Temperature

Work: -15℃ ~ 55℃ Storage: -25℃ ~ 70℃

Humidity

Relative humidity ≤93%

Altitude

≤2500m

Communication

RS485/Modbus-RTU

Installation

DIN35mm guide rail or baseplate mounted


Protection level

IP20

Pollution levels

2

 

 

Security

Insulation

All terminals and the insulation resistance between the conductive pieces

not below 100 m Ω

 

Pressure

A voltage current signal // B voltage current signal // Other ports meet AC2kV 1min between pairs,leakage current should be less than 2mA,no

breakdown or flashering phenomenon.

 

Electromagnetic compatibility

Anti-static

interference

Class 4

Radio frequency

electromagnetic radiation

 

Class 3

Note: The secondary input voltage of dc incoming and outgoing modules is 5V,and the default value of primary side current is 50A.If the Hall sensor is different,the customer can set the ratio through the touch screen according to the actual use.


Technical parameters

AMC16Z-FDK24

AMC16Z-FDK48

Measured parameter

Voltage,current,power,electrical energy,switching state

 

 

Bus voltage

Ratetd

48VDC,240VDC,336VDC

Measured range

±20%

Overload

Instantaneous voltage 2 times per second

 

Currentoutcoming line circuit

Ratetd

 

5V (Hall sensor,external power supply ±12V)

Range


Overload

Duration 1.2 times,instantaneous 10 times/second

Measurement precision

 

Outgoing line

 

Voltage/current level 0.5,power/electric energy level 1

Auxiliary power

Get power supply from AMC16Z-ZD

 

 

Environment

Temperature

Work: -15℃ ~ 55℃ Storage: -25℃ ~ 70℃

Humidity

Relative humidity ≤93%

Altitude

≤2500m

Communication

RS485/Modbus-RTU

Installation

DIN35mm guide rail or baseplate mounted

Protection level

IP20

Pollution levels

2

 

 

Security

Insulation

All terminals and the insulation resistance between the conductive pieces not below 100 m Ω

 

Pressure

A voltage current signal // B voltage current signal // Other portsmeet AC2kV 1min between pairs,leakage current should be less than 2mA,

no breakdown or flashing phenomenon.

 

Electromagnetic compatibility

Anti-static interference

Class 4

Radio frequency electromagnetic

radiation

 

Class 3

Note: The secondary input voltage of AMC16Z-FDK module is 5V,and the default value of the primary side current is 50A.If the Hall sensor is different,the customer can set the ratio through the touch screen according to the actual use.


Active switching module

Technical parameters

AMC16Z-KA

Input frequency

45-60Hz

Auxiliary power

Get power supply from AMC16Z-ZD

Power frequency withstand voltage

AC 2kV/1min 50Hz between power/input signal ports

 Environment

Temperature

Work: -15℃ ~ 55℃ Storage: -25℃ ~ 70℃

Humidity

Relative humidity ≤93%

Altitude

≤2500m

Switching input

48-way wet contact(48VDC,240VDC,336VDC)

Communication

RS485/Modbus-RTU

Installation

DIN35mm guide rail or baseplate mounted

Protection level

IP20

Pollution levels

2

 

 

 

 

Security

Insulation

All terminals and the insulation resistance between the conductive pieces not below 100 m Ω

 

 

Pressure

The input signal of a-channel switching quantity // B-channel switching quantity input signal // other ports should meet AC2kV 1min between pairs,the leakage current should be less than 2mA,

and there is no breakdown or flashing phenomenon.

 

Electromagnetic compatibility

Anti-static interference

Class 4

Radio frequency

electromagnetic radiation

 

Class 3


Passive switching module

Technical parameters

AMC16Z-KD

Input frequency

45-60HZ

Auxiliary power

Get power supply from AMC16Z-ZD

Insulation Resistance

100MΩ

 

Environment

Temperature

Work: -15℃ ~ 55℃ Storage: -25℃ ~ 70℃

Humidity

Relative humidity ≤93%

Altitude

≤2500m

Switching input

48-way dry contact

Communication

RS485/Modbus-RTU

Installation

DIN35mm guide rail or wall mounted installation

Protection level

IP20

Pollution levels

2

 

 

Security

Insulation

All terminals and the insulation resistance between the conductive pieces not below 100 m Ω

 

Pressure

The input signal of a-channel switching quantity // B-channel switching quantity input signal // other ports should meet AC2kV 1min between pairs,the leakage current should be less than 2mA,and there is no

breakdown or flashing phenomenon.

Electromagnetic

Anti-static

Class 4


Extension power module

Technical parameters

AMC16Z-DC48V

 

Input

Voltage

48VDC

Range

±20%

 

 

Output

Voltage

12VDC

Current

1A

Maximum output

 

12W

 

Environment

Temperature

Work: -15℃ ~ 55℃ Storage: -25℃ ~ 70℃

Humidity

Relative humidity ≤93%

Altitude

≤2500m

Installation

DIN35mm guide rail or baseplate mounted

Protection level

IP20

Pollution levels

2

Security

Insulation

All terminals and the insulation resistance between the conductive pieces not below 100 m Ω

 

Pressure

A circuit voltage and current signal // B circuit voltage and current

signal // Supply output should meet AC2kV for 1min,leakage current should be less than 2mA,no breakdown or flashing phenomenon.

 

 

 

 

Electromagnetic compatibility

Anti-static interference

Class 4

Resistance to rapid

transient pulse groups

 

Class 3

Resistant to surge interference

Class 4

Radio frequency

electromagnetic radiation

 

Class 3

 

Technical parameters

AMC16Z-DC240/336V

Input

Voltage range

 

DC180-410VDC

 

Output

Voltage

12VDC

Current

1A

Maximum output power

12W

 

Environment

Temperature

Work: -15℃ ~ 55℃ Storage: -25℃ ~ 70℃

Humidity

Relative humidity ≤93%

Altitude

≤2500m

Installation

DIN35mm guide rail or baseplate mounted

Protection level

IP20

Pollution levels

2

Security

Insulation

All terminals and the insulation resistance between the conductive pieces not below 100 m Ω



 

Pressure

A circuit voltage and current signal // B circuit voltage and current signal // Supply output should meet AC2kV for 1min,leakage current should be less than 2mA,no breakdown or flashering

phenomenon.

 

 

 

Electromagnetic compatibility

Anti-static interference

Class 4

Resistance to rapid transient pulse

groups

 

Class 3

Resistant to surge interference

Class 4

Radio frequency electromagnetic

radiation

 

Class 3


Products