Industrial Electrical Insulation Safety Meters

0

LCD Display

1

Appearance

2

Wiring

3

Typical connection


5


Dimension drawings of Industrial Electrical Insulation Safety Meters

AIM-T500L (unit: mm)

   

Front view                            Side view

Back view


ASG200 (unit: mm)

   

Front view                              Side view


AIL200-12 (unit: mm) 

   

Front view                              Side view


AKH-0.66L series current transformer dimension are shown in the table below:

Type

 

Rated currentA

A/mm

B/mm

C/mm

D/mm

E/mm

F/mm

G/mm

H/mm

Weight /kg

L45

16~100

74

22.5

4.5

4

45

65

75

64.5

0.18

L80

100~250

120

23

4.5

4

80

105

120

104.5

0.42

L100

250~400

140

23

4.5

4

100

124

140

123.5

0.50

L150

400~800

204

24

4.5

6

150

160

197

173.5

1.32

L200

800~1500

246

28

4.5

6

200

210

241

213.5

1.94

Note: The current transformer with corresponding specifications should be selected according to the rated current of the circuit and the thickness of the wire. (If you have special requirements on the shape and range of the transformer, contact us)




Typical connection of Industrial Electrical Insulation Safety Meters


With the development of industrial science and technology, residual current poses a great threat to industrial production safety. In order to improve the continuity and reliability of power supply, many important production sites adopt IT distribution system (ungrounded system).

AIM-T500L series industrial insulation monitoring and fault location system is specially developed by Acrel for IT distribution system in industrial occasions such as mine, glass factory, electric furnace and test equipment, ship, metallurgical plant, chemical plant, explosion hazard site, computer center and emergency power supply. The system has rich functions, including insulation resistance monitoring, insulation fault warning, insulation fault alarm, event recording, parameter setting, communication networking, etc. When the system has grounding fault, it can give a timely alarm and accurately locate the specific circuit of the fault to remind staff to check the fault in time.  

The products conform to the requirements of enterprise standard Q/VDCL-26-2017 IT System Insulation Monitor.




Function description of Industrial Electrical Insulation Safety Meters

AIM-T500L insulation monitor

1) Monitor the insulation resistance of IT system in real time, warning or alarm when the resistance exceeds the limit;

2) Relay alarm output, LED alarm output and other fault indication modes;

3) SOE function, convenient for staff to check and analyze the failure type and occurrence time, and judge the operation status of the system;

4) Self-check function, which can realize fault self-check of instrument hardware circuit;

5) Disconnect monitoring, real-time monitoring of PE/KE function grounding wire connection status;

6) RS485 interface, standard Modbus-RTU protocol;

7) CAN interface, custom protocol, used to interact with signal generator and fault locator;

8) Support manual/automatic reset modes;

9) Wide range of applications, suitable for AC, DC and AC-DC hybrid IT systems.


ASG200 test signal generator

1) Generate positioning signals and inject them into the ungrounded system;

2) Indicate the phase line where the fault is;

3) Manual startup positioning is supported;

4) CAN bus technology is adopted to facilitate data interaction with other devices in the system.


AIL200-12 insulation fault locator

1) Locate and indicate the loop where the fault is;

2) A single AIL200-12 can locate up to 12 loops;

3) Each IT system can be connected to a maximum of 90 locators, with a total of 1080 loops;

4) CAN bus technology is adopted to facilitate data interaction with other devices in the system.


AKH-0.66L series current transformer

1) Rated current ratio 5A:5mA, ratio 1000:1, select the appropriate aperture according to the rated current of the loop;

2) Coordinate with AIL200-12 insulation fault locator to achieve fault location.


Technical parameter of Industrial Electrical Insulation Safety Meters


6


AIM-T500L insulation monitor

Accessory power supply

Voltage

AC85~265V

DC100~300V

Voltage range

System voltage

AC 0~690V

DC 0~800V

Power dissipation

<8W


Frequency range

40~460Hz

Insulation monitoring

Measuring range

1k~10MΩ

Environment

Working temperature

-15~+55℃

Alarm range

10k~10MΩ


Storage temperature

-20~+70℃

Response time (Ce=1μF)

<5s


Relative humidity

<95%, without condensation

system leakage capacitance

<500μF


Altitude

≤2500m

Internal parameters

Measuring voltage

<50V

Output

Relay output

Error, warning, Alarm

Measuring current

<270μA

Communication

RS485, Modbus-RTU

CAN, custom protocol

Internal DC impedance

≥180kΩ

Rated impulse voltage /Pollution Level

8kV/Ⅲ


ASG200 test signal generator

Accessory power supply

Voltage

AC 85~265V

DC100~300V

Power dissipation

<7W

IT system

Voltage

AC 220V

3AC 0~690V

DC 0~800V

Fault locating

Response time

<5s

positing voltage

20V/5Hz

positing current

0~10mA

Response sensitivity

——

Internal parameters

EMC/ Radiation

IEC61326-2-4

Output

Relay output

——

Environment

Working temperature

-15~+55℃


AIL200-12 insulation fault locator

Accessory power supply

Voltage

AC 85~265V

DC100~300V

Power dissipation

<5W

IT system

Voltage

——

Fault locating

Response time

<12s

positing voltage

——

positing current

——

Response sensitivity

>0.5mA

Internal parameters

EMC/ Radiation

IEC61326-2-4

Output

Relay output

Alarm

Environment

Working temperature

-15~+55℃


AKH-0.66L series current transformer

specifications

Rated current

Ratio

Accurate level

rated load

Overload ratio

L-45

16-100A

5A:5mA

1 level

100Ω

10

L-80

100-250A

L-100

250-400A

L-150

400-800A

L-200

800-1500A


7

RELATED PRODUCTS

Products

Copyright © 2021 Acrel Co., Ltd. All Rights Reserved.