Home » Products » Universal Motor Controller » Motor control and protection unit
Share to:

Motor control and protection unit

● U, I, P, S, PF, F, EP, Leakage, PTC/NTC
● 16 protect function
● Start control function
● 9 programmable DI
● 5 programmable DO
● Modbus-RTU or Profibus-DP communication
● 1 DC4-20mA analog output
● 20 fault record
● Anti-shaking function
 
CE
Quantity:

Motor control and protection unit

Characteristic

7

8

9

Communication

Display

Rated U and I

RS485 (Modbus-RTU)

LCD display for U, I, P, Q etc

AC380/660V, rated current up to 800A

Function


Accuracy
U, I: Class 1.5
 
Frequency
Range: 45-65Hz
 
Auxiliary power supply
AC85V-265V/DC100V-350V
 
SOE event recorder
Record 8 fault messages
1


2 Installation:
1. Main body: DIN 35mm
2. Display unit: Panel mounted
 
Dimension(L*W*H):
81.5mm*86mm*90mm

Appearance

3

Operation Instruction



4

Dimensions

5

6



Dimension drawings of Motor control and protection unit

Appearance and size of mounting hole



Front View             Left view

Top view


Installation dimension of protector display unit

Panel opening


Anti sway electric module


AC380 power module




Typical connection of Motor control and protection unit


Smart motor protectors ARD2F series (hereinafter referred to as the protector), utilizes advanced single-chip microcomputer technology which has many features like strong anti-interference, stable and reliable running, digitalization, intelligence and networking, etc. Protector can protect motors from many faults during the motor running such as timeout startup, overload, locked rotor/block, phase failure, unbalance, under-load, earthing, earth leakage, over voltage, under voltage, phase sequence, overpower, under power, temperature, external faults, etc. and is equipped with SOE fault event log function which is convenient for maintenance stuff to find the causes of the problems, and display the running state clearly and intuitively through LCD in Chinese in four lines, status indicators and other ways. It is suitable for coal mine, petrochemical industry, metallurgy industry, power industry, shipbuilding, civil buildings and other fields. The protector has RS485 remote communication interface and DC4-20mA analog output, which is convenient to form a network system together with  control machines like PLC and PC to realize the remote monitoring of motor.




Function description of Motor control and protection unit

No.

Main menu

Function

Sort

Setting ranges

Default value

Unit

 

I

Alarm infromation






 

II

Trip Information






 

 

III

 

Operation INFORMAT ION

 

 

1 this run




 

 

h


2 this




h


(3) Running




h


stopping time




h


number of starts






6 Number of trips





 

IV

system parameter

 

1 Baud rate


2400、4800、9600、

19200、38400

 

9600

 

bps


2 Postal


1-247

1



3 Enter the password


 

0-9999

 

1



 

4 Motor Type


 

General motor, safety-increased motor

 

Common motor



5

Transmission Type


la, Ib, Ie, lay, Uab,

Ubc, Uca, Uay, PTC, heat Capacity, P, F

 

lay



6 transmission ratio


 

1-8

 

2



7 backlight lit


On/off

OFF



8.System voltage


 

380、660

 

380

 

V


9.Rated frequency


 

45-65

 

50


 



 

 

 

10.Rated power


 

0.4-1.6

1.6-6.3

6.3-25

25-100

63-250

250-800

 

1056、

4158、

16500、

66000、

165000、

480000

 

 

 

 

w


11.CT ratio


1-1000

1



12 local speed switch


 

On/off

 

OFF



13.fundament al wave

switch


 

On/off

 

OFF



14.Software Version

No.





 

V

Protection parameter

1. starting protection

 

Starting time

 

0.1-999.9

 

10.0

 

s



Alarm

On/off

OFF




Trip

On/off

ON



2.overload

protection

Rated current

of motor

0.1-1.6

1.6-6.3

 

A





6.3-25

25.0





25-100

100





63-250

250





250-800

800




Trip class

l, 2,3,5,10,15,20

5

Level




25303540






23456810

2

s




1215





Alarm

threshold

 

1-99%

 

85

 

%



Alarm

On/off

OFF




Trip

On/off

ON




Overload

automatic

 

On/off

 

OFF






Cooling time

1-30

30

min


3 under load

protection

Alarm

threshold

 

10-99%

 

70

 

%



Trip threshold

value

 

10-99%

 

50

 

%



Trip delay

0.1-600

5.0

s



Alarm

On/off

OFF




Trip

On/off

OFF



4Phase failure

protection

 

Trip delay

 

0.1-600

 

1.0

 

s



Alarm

On/off

OFF




Trip

On/off

ON



5 phase

sequence

 

Trip delay

 

0.1-600

 

1.0

 

s



Alarm

On/off

OFF




Trip

On/off

ON



6 unbalance

protection

Alarm

threshold

 

10-80%

 

20

 

%



Trip threshold

value

 

10-80%

 

30

 

%



Trip delay

0.1-600

5.0

s



Alarm

On/off

OFF




Trip

On/off

OFF



7 Earthing /

Earth leakage

Transformer

input

 

On/off

 

OFF




Earthing

alarm

 

20-100%

 

20

 

%



Earthing trip

threshold

 

20-100%

 

50

 

%



Trip delay

0.1-600

0.1

s



Earth leakage

alarm current

 

100-1000

 

200

 

rnA



Earth leakage

trip current

 

100-1000

 

300

 

rnA



Trip delay

0.1-600

0.5

s



Alarm

On/off

OFF






Trip

On/off

OFF



8

Short-Circuit

Alarm

threshold

400-700% max.

measurable overload times

 

400

 

%



Trip threshold

value

400-700% max.

measurable overload times

 

500

 

%



Trip delay

0.1-600

0.1

s



 

Alarm

 

On/off

 

OFF




 

Trip

 

On/off

 

OFF



9 Over

voltage

Alarm

threshold

 

110-150%

 

110

 

%



Trip threshold

value

 

110-150%

 

120

 

%



 

Trip delay

 

0.1-600

 

5.0

 

s



 

Alarm

 

On/off

 

OFF




 

Trip

 

On/off

 

OFF



10 Under

voltage

Alarm

threshold

 

55-90%

 

90

 

%



Trip threshold

value

 

55-90%

 

80

 

%



 

Trip delay

 

0.1-600

 

5.0

 

s



Alarm

On/off

OFF




 

Trip

 

On/off

 

OFF



11 Pei-rotor

protection

Alarm

threshold

 

100-700%

 

500

 

%



Trip threshold

value

 

100-700%

 

600

 

%



 

Trip delay

 

0.1-600

 

5.0

 

s



 

Alarm

 

On/off

 

OFF




 

Trip

 

On/off

 

OFF



12 blocking

protection

Alarm

threshold

 

100-700%

 

150

 

%





Trip threshold

value

 

100-700%

 

250

 

%



 

Trip delay

 

0.1-600

 

5.0

 

s



 

Alarm

 

On/off

 

OFF




 

Trip

 

On/off

 

OFF



 

13 overpower protection

Alarm

threshold

 

100-700%

 

150

 

%








Trip threshold

value

 

100-700%

 

250

 

%



 

Trip delay

 

0.1-600

 

5.0

 

s



 

Alarm

 

On/off

 

OFF




 

Trip

 

On/off

 

OFF



 

14 under power protection

Alarm

threshold

 

0-100%

 

80

 

%








Trip threshold

value

 

0-100%

 

50

 

%



 

Trip delay

 

0.1-600

 

5.0

 

s



 

Alarm

 

On/off

 

OFF




 

Trip

 

On/off

 

OFF



15

temperature

 

PTC type

 

On/off

 

ON




Return

resistance

 

0 closed 1000-30000

 

0

 

Ω



Alarm

100-30000

1600

Ω



Trip

100-30000

3600

Ω



Trip delay

0.1-600

5.0

s



Alarm

On/off

OFF




Trip

On/off

OFF



16 External

Trip delay

0.1-600

5.0

s





Alarm

On/off

OFF




 

Trip

 

On/off

 

OFF


 

VI

Control parameter

l control authority

Switching input

local, on-site, remote

I. Full-controlled

Full-controlle d



(2) Starting Control.

 

Starting Mode

Protection mode, manual mode, two-step

Mode, two-speed mode

protection mode




Starting -

delay

0.1-600

3.0

s


self-start

Self-start

Mode

reset/ start

Starting




Self-start

delay

0.1-600

5.0

s



Self-start control

 

On/off

 

OFF



4 Loss

voltage

75-95%

80

%



Immediately restarting power failure

time

 

 

0.1-0.5

 

 

0.1

 

 

s



Allowable

0.5-10.0

5.0

s



Restarting

1.0-60.08

30.0

s



Controls

0 OFF, 1 start 1, 2 start2

OFF



5 reflow

inspection

Delay setting

0.1-600


s



Controls

On/off

OFF



 

 

 

 

 

 

6 D03

programmabl e Setting

 

 

 

 

 

 

 

Programmabl e setting

 

- Start 1,

- Start

- alarm fault output, 4 - trip fault output,

- device self-checking output

- device power output, 7 - stopping state ready 8 - running state output, 9-DI control output,

10 - Bus control

 

 

 

 

 

 

 

3




Action time

setting

 

0-250

 

0.1

 

s




 

 

 

 

 

7D04

programmabl e Setting

 

 

 

 

 

 

Programmabl e setting

 

- Starting1,

- Start 2,

- alarm fault output, 4 - trip fault output,

- device self-checking output

- device power output, 7 - stopping state ready 8 - running state output, 9-DI control output,

10 - Bus control

 

 

 

 

 

 

 

3




Action time setting

 

0-250

 

0.1

 

s



Trip fault setting

 

0-65535

 

65535



 

 

 

 

 

 

 

8DI9

programmabl e Setting

 

 

 

 

 

 

 

DI9

programmabl e setting

l common DI

Start 1 ( direct start, turn left,

low speed

start 2 ( turn right, high speed),

shutdown

Resetting,

Emergency shutdown

external fault 8 start / stop,

control authority 1

10 control authority 2

11 two-wire start-stop




9TEST

D02

On/off

OFF




D03

On/off

OFF




D04

On/off

OFF




D05

On/off

OFF





Technical parameter of Motor control and protection unit

10

Technical parameters

Technical specification

Auxiliary power supply of protector

 

AC85V~220VIDCI00~350V, power consumption 15VA

Rated working voltage of motor

AC380V/AC660V, 50Hz/60Hz

 

 

 

 

Rated working current of motor

lA(O.1A-9999A)

 

 

 

Small special current transformers

5A(O.IA-9999A)

1.6A(OAA-1.6A)

6.3A(1.6A-6.3A)

25A (6.3A-25A)

100A (25A-100A)

250A (63A-250A)

Special current transformers

800A (250A-800A)

Relay output contactor, rated negative capacity

 

5, AC250V、6A

Switching input

9, opto-coupler insolation

Telecommunication

RS485 Modbus RTU、Profibus DP protocol

 

 

 

Environment

Working Temperature

-1O°C~55°C

Storage temperature:

-20℃-18mm

Relative humidity

5%~95% no condensation

Altitude

≤200m

Classes of pollution

Level 2

Protection level

Main part IP20, display unit IGIP45

Installation category

Class III



11