Motor management controller

● Suitable for motors with rated voltage of AC380V/660V;
● Optional leakage protection, RS485 communication, analog output, etc.
● 2 channels DI passive dry node input, signal power supply with built-in DC24V power supply;
● 4 channels DO output.
 
CE
Quantity:

Motor management controller


Characteristic

7

8

9

Communication

Display

Rated U and I

RS485 (Modbus-RTU)

4 digitals LED display

AC380/660V, rated current up to 800A




Function


Accuracy
Active energy: Class 0.5
 
Frequency
Range: 45-65Hz
 
Auxiliary power supply
AC/DC 85~265V
 
Pulse output
1600-160000imp/kWh
 
Consumption
Voltage: Power consumption <0.5VA;
Current: Power consumption< 0.5VA;
Auxiliary power supply:power consumption≤10VA
1
2 Installation:
Panel mounted
 
Dimension(L*W*H):
96mm*78.5mm*48mm

Appearance


3

Wiring


4


5



Dimension drawings of Motor management controller

Appearance of main part control module, as shown in figure 1.

      

Figure 1 ARD3 Main part control module dimension


Mounting dimension of protector display unit

Figure 2 Mounting dimension of protector display unit


Transformer mounting dimension of less than 100A

Figure 3 Transformer mounting dimension of less than 100A


Outline dimensions of 250A outlay current transformer

Figure 4 Outline dimensions of outlay current transformer


Outline dimensions of 800A outlay current transformer

Figure 5 outline dimensions of outlay current transformer


Outline dimensions of residual current transformer

Zero sequence current transformer


Outline dimensions of Anti sway electric module

Figure 8 Outline dimensions of Anti sway electric module


Outline dimensions of AC380 power module

Figure 9 Outline dimensions of AC380 power module




Typical connection of Motor management controller



ARD3 series intelligent motor protectors (hereinafter referred to as the protector), adopt advanced single-chip microcomputer technology which has many features like strong anti-interference capability, stable and reliable performance, digital, intelligent and networked, etc. Protector can protect motors from many faults during the motor running such as starting timeout, overload, locked rotor/block, phase failure, unbalance, under load, grounding, earth leakage, over voltage, under voltage, phase sequence, overpower, under power, temperature, external faults, etc. and is equipped with SOE fault event log function which is convenient for maintenance stuff to find the causes of the problems, and display the running  state clearly and intuitively through LCD in Chinese in four lines, status indicators and other ways. It is suitable for coal mine, petrochemical, metallurgy, electric power, shipbuilding, civil construction and other fields. The protector has RS485 remote communication interface and DC4-20mA analog output, which is convenient to form a  network system together with control machines like PLC and PC to realize the remote control of motor running.




Function description of Motor management controller

No.

Main menu

Function

Sort

Setting ranges

Default value

Unit

 

1

Alarm infromation






2

Trip

Information






 

 

 

 

 

 

 

3

 

 

 

 

 

 

 

Operation Information

 

1 this run




 

h

2 this stopping




h

 

3 Running Time




 

h

 

4 stopping time




 

h

 

5 number of starts





 

6 Number of Trips





 

 

 

 

 

 

 

 

 

 

 

4

 

 

 

 

 

 

 

 

 

 

 

system parameter

1 Baud rate


2400、4800、9600、

19200、38400

9600

bps

2 Postal address


1-247



3 password


0-9999



4 Motor Type


General motor,

safety-increased motor

Common

motor


 

5 Transmission Type


la, Ib, Ie, lay, Uab,

Ubc, Uca, Uay, PTC, heat

Capacity, P, F

 

 

lay


6 transmission ratio


1-8

2


7 backlight lit


On/off

OFF


8 System voltage


380、660

380

V

9 Rated frequency


45-65

50


 

10 Rated power


0.4-1.6

1056、


1.6-6.3

4158、







6.3-25

16500、

w

25-100

66000、





63-250

165000、


250-800

480000


11.CT ratio


1-1000

1


12 local speed

switch


On/off

OFF


13.fundamental wave switch


 

On/off

 

OFF


14.Software

Version No.





 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Protection parameter

 

 

1. starting

protection

Starting time

0.1-999.9

10.0

s

Alarm

On/off

OFF


Trip

On/off

ON


 

 

 

 

 

 

 

 

 

 

 

2 overload

protection

 

 

 

Rated current of motor

0.1-1.6

1.6-6.3

6.3-25

25-100

63-250

250-800

1.6

6.3

25.0

100

250

800

 

 

 

A

 

 

Trip class

l, 2,3,5,10,15,20 25303540

 

5

 

 

Level

23456810

1215

2

 

Alarm threshold value

 

1-99%

 

85

 

%

Alarm

On/off

OFF


Trip

On/off

ON


 

Overload automatic reset

 

On/off

 

OFF


 

Cooling time

 

1-30

 

30

 

min

 

 

 

3 under load protection

 

Alarm threshold value

 

10-99%

 

70

 

%

 

Trip threshold value

 

10-99%

 

50

 

%

 

Trip delay

 

0.1-600

 

5.0

 

s





Alarm

On/off

OFF


Trip

On/off

OFF


 

 

4 Phase failure protection

 

Trip delay

 

0.1-600

 

1.0

 

s

Alarm

On/off

OFF


Trip

On/off

ON


 

 

5 phase sequence protection

 

Trip delay

 

0.1-600

 

1.0

 

s

Alarm

On/off

OFF


Trip

On/off

ON


 

 

 

 

6 imbalance protection

 

Alarm threshold value

 

10-80%

 

20

 

%

 

Trip threshold value

 

10-80%

 

30

 

%

 

Trip delay

 

0.1-600

 

5.0

 

s

Alarm

On/off

OFF


Trip

On/off

OFF


 

 

 

 

 

 

 

 

 

 

7 Grounding / Earth leakage

 

Transformer input

 

On/off

 

OFF


Grounding alarm

threshold value

 

20-100%

 

20

 

%

Grounding Trip

threshold value

 

20-100%

 

50

 

%

 

Trip delay

 

0.1-600

 

0.1

 

s

Earth leakage alarm

current

 

100-1000

 

200

 

rnA

Earth leakage Trip

current

 

100-1000

 

300

 

rnA

 

Trip delay

 

0.1-600

 

0.5

 

s

 

Alarm

 

On/off

 

OFF


 

Trip

 

On/off

 

OFF


 

8 Short-Circuit Protection

 

Alarm threshold value

400-700% max.

measurable overload

 

400

 

%

 

Trip threshold value

400-700% max.

measurable overload

 

500

 

%





 

Trip delay

 

0.1-600

 

0.1

 

s

 

Alarm

 

On/off

 

OFF


 

Trip

 

On/off

 

OFF


 

 

 

 

 

9 Over voltage protection

 

Alarm threshold value

 

110-150%

 

110

 

%

 

Trip threshold value

 

110-150%

 

120

 

%

 

Trip delay

 

0.1-600

 

5.0

 

s

 

Alarm

 

On/off

 

OFF


 

Trip

 

On/off

 

OFF


 

 

 

 

 

10 Under voltage protection

 

Alarm threshold value

 

55-90%

 

90

 

%

 

Trip threshold value

 

55-90%

 

80

 

%

 

Trip delay

 

0.1-600

 

5.0

 

s

 

Alarm

 

On/off

 

OFF


 

Trip

 

On/off

 

OFF


 

 

 

 

 

11 lock-rotor protection

 

Alarm threshold value

 

100-700%

 

500

 

%

 

Trip threshold value

 

100-700%

 

600

 

%

 

Trip delay

 

0.1-600

 

5.0

 

s

 

Alarm

 

On/off

 

OFF


 

Trip

 

On/off

 

OFF


 

 

 

12 blocking protection

 

Alarm threshold value

 

100-700%

 

150

 

%

 

Trip threshold value

 

100-700%

 

250

 

%

 

Trip delay

 

0.1-600

 

5.0

 

s





 

Alarm

 

On/off

 

OFF


 

Trip

 

On/off

 

OFF


 

 

 

 

 

 

13 overpower protection

 

 

Alarm threshold value

 

 

100-700%

 

 

150

 

 

%

 

Trip threshold value

 

100-700%

 

250

 

%

 

Trip delay

 

0.1-600

 

5.0

 

s

 

Alarm

 

On/off

 

OFF


 

Trip

 

On/off

 

OFF


 

 

 

 

 

 

14 under power protection

 

Alarm threshold value

 

0-100%

 

80

 

%

 

Trip threshold value

 

0-100%

 

50

 

%

 

Trip delay

 

0.1-600

 

5.0

 

s

 

Alarm

 

On/off

 

OFF


 

Trip

 

On/off

 

OFF


 

 

 

 

 

15 temperature protection

 

PTC type

 

On/off

 

ON


 

Return resistance value

 

0 closed 1000-30000

 

0

 

Ω

Alarm resistance value

100-30000

1600

Ω

Trip resistance value

100-30000

3600

Ω

Trip delay

0.1-600

5.0

s

Alarm

On/off

OFF


Trip

On/off

OFF


 

16 External fault

Trip delay

0.1-600

5.0

s

Alarm

On/off

OFF


Trip

On/off

OFF


 

6

 

Control parameter

 

1 control authority

 

On-off input

local, on-site, remote ,

Full-controlled

 

Full-controlled






 

2 Starting Control.

 

Starting Mode

Protection mode, manual mode, two-step

Mode, two-speed mode

protection mode



 

 

 

 

 

3 self-start

 

Starting - delay

 

0.1-600

 

3.0

 

s

Self-start Mode

reset/ start

Starting


Self-start delay

0.1-600

5.0

s

 

Self-start control

 

On/off

 

OFF


 

 

 

 

4 Loss voltage restarting

voltage setting

75-95%

80

%

Immediately restarting power failure time

 

0.1-0.5

 

0.1

 

s

Allowable time (min)

0.5-10.0

5.0

s

Restarting delay

1.0-60.08

30.0

s

Controls

0 OFF, 1 start 1,

2 start2

OFF


 

5 reflow inspection

Delay setting

0.1-600


s

Controls

On/off

OFF


 

 

 

 

 

 

 

 

6 DO3

Programmable Setting

 

 

 

 

 

 

 

 

Programmable setting

 

 

- Start 1,

- Start

- alarm fault output, 4 - Trip fault output,

- device self-checking output

- device power output, 7 - stopping state ready 8 - running state output, 9-DI control output,

10 - Bus control

 

 

 

 

 

 

 

 

3


 

Action time setting

 

0-250

 

0.1

 

s




 

 

 

 

 

 

 

 

 

7 DO4

programmable Programmable Setting

 

 

 

 

 

 

 

Programmable setting setting

 

 

1 - Start ing1, 2 - Start 2,

3 - alarm fault output, 4 - Trip fault output,

- device self-checking output

- device power output, 7 - stopping state ready 8 - running state output, 9-DI control output,

10 - Bus control

 

 

 

 

 

 

 

 

3


 

Action time

 

0-250

 

0.1

 

s

 

Trip setting

 

0-65535

 

65535


 

 

 

 

 

 

 

8 DI9

programmable Setting

 

 

 

 

 

 

 

DI9 programmable setting

l common DI

Start 1 ( direct start, turn left,

low speed

start 2 ( turn right, high speed),

Stop

Resetting,

Emergency Stop

external fault 8 start / stop,

control authority 1

10 control authority 2

11 two-wire start-stop

 

 

 

 

 

 

 

 

1


 

9 TEST

DO2

On/off

OFF


DO3

On/off

OFF


DO4

On/off

OFF


DO5

On/off

OFF



Technical parameter of Motor management controller

6

Technical parameters

Technical index

Auxiliary power supply of the

AC 85V~220V ,DC I00V~350V, power dissipation 15VA

Motor rated operating voltage

AC 220V/380V/AC660V, 50Hz/60Hz

 

 

 

 

Motor rated operating current

lA(0.IA-9999A)

 

 

Small special current transformers are used.

5A(0.IA-9999A)

1.6A(0A-1.6A)

6.3A(1.6A-6.3A)

25A (6.3A-25A)

I00A (25A-100A)

250A (63A-250A)

 

Special current transformers are used.

800A (250A-800A)

Relay output contactor Capacity

5 DO,resistive load

AC250V、6A

On-off input

9 DI, opto-coupler insolation

Telecommunication

RS485 Modbus RTU、Profibus DP protocol

 

 

Environment

Working Temperature

-10°C~55°C

Storage temperature:

-20°C~70°C

Relative humidity

5%~95% no condensation

Altitude

≤2000m

Classes of pollution

Level 2

Degree of protection

Main part IP20, display unit IP45

Installation category

Class III


7