   Mobile:86-13611976994
  E-mail:Grace@acrel.cn
Home » Products » Energy Quality Improvement » Power quality management PQMS devices
Share to:

Power quality management PQMS devices

● 380V±15%,50Hz±2%
● Full response time ≤ 5ms
● 30kVA,50kVA,75kVA or 100kVA
● RS485(Modbus-RTU)or Ethernet(Modbus-TCP)
● Frozen data
Quantity:

Power quality management PQMS devices

1

Function



1)Flexible compensation method:Compensating for reactive power from the load,filter out harmonics within 5th, 7th, 9th, 11th, and 13th;

2)Ability of managing three-phase imbalance;

3)Linear compensation,Response time ≤ 5ms;

4)Humanized human-computer interaction interface, which displays real-time power quality information of the system and the ontology. This interface has the ability to control the device remotely and easy to operate;

5)Adopt imported IGBT which has high power density and high reliability;

6)Using DSP digital control system for high speed detection and calculation;

7)With remote communication interface, real-time monitoring through PC;

8)Standard modular design which reduces lead times and increases reliability and maintainability.



3

Dimension(L*W*H)

450*622*201mm

Response time

Full response time≤5ms,Instantaneous response time≤100μs

Total harmonic compensation rate

≥0.99,Compensates for capacitive reactive and inductive reactive

Self-loss

≤2%

Efficiency

≥98%

Switching frequency

20KHz


Appearance

4

Interface

Main interface

5

System information interface

6

Fault information interface

7

Parameter setting interface


8

Wiring

 

9



Dimension drawings of Power quality management PQMS devices

Views from all directions of the ANSVG module chassis

ANSVG-50kvar, ANSVG-75kvar module chassis front view

Side view of ANSVG-50kvar, ANSVG-75kvar module chassis

Top view of ANSVG-50kvar, ANSVG-75kvar module chassis

               

Side view of ANSVG-50kvar, ANSVG-75kvar wall-mounted module chassis             ANSVG-50kvar, ANSVG-75kvar wall-mounted module chassis front view

Top view of ANSVG-50kvar, ANSVG-75kvar wall-mounted module chassis

ANSVG-100kvar module chassis front view

Side view of ANSVG-100kvar module chassis

Top view of ANSVG-100kvar module chassis

  

Side view of ANSVG-100kvar wall-mounted module chassis      ANSVG-100kvar wall-mounted module chassis front view

Top view of ANSVG-100kvar wall-mounted module chassis


ANSVG Full machine chassis view from all directions

    

ANSVG front view of the whole machine          ANSVG machine side view 

   

ANSVG top view of the whole machine           ANSVG rear view of the whole machine 




Typical connection of Power quality management PQMS devices



Static var generator is a new type of power electronic device used for reactive power compensation, harmonic control and unbalance adjustment.

The basic principle of the static var generator is shown in Figure 2-18: the voltage and current of the compensation object are detected, the command signal of the compensation current is calculated by the command current calculation circuit, and the signal is amplified by the compensation current generation circuit to obtain the compensation The compensation current is offset with the reactive current to be compensated in the load current, and finally the desired power supply current is obtained. Its application can overcome the slow response speed of traditional reactive power compensators such as LC compensators, the compensation effect cannot be accurately controlled, and it is easy to communicate with the power grid. Shortcomings such as parallel resonance and switching oscillation occur. The basic principle is that the three-phase bridge circuit is directly connected in parallel to the power grid through a reactor, and the phase and amplitude of the AC side output voltage of the bridge circuit are appropriately adjusted or the AC side current is directly controlled, so that the circuit can absorb or Send out the reactive current that meets the requirements to achieve the purpose of dynamic reactive power compensation. 




Function description of Power quality management PQMS devices

1) Flexible compensation method: compensate load reactive power, filter out harmonics within 5, 7, 9, 11, and 13 times;

2) Three-phase imbalance can be treated;

3) Linear compensation, response time ≤5ms;

4) Humanized human-computer interaction interface, through which the real-time power quality information of the system and the main body can be seen, the operation is simple, and it can be controlled remotely or locally;

5) Imported IGBT is adopted, which has high power density and high reliability;

6) Digital control system adopting DSP high-speed detection and calculation;

7) The monitoring and display have a remote communication interface, which can be monitored in real time through a PC;

8) Standard modular design shortens the delivery cycle, while improving the reliability and maintainability of use. 


Technical parameter of Power quality management PQMS devices


11

1.Rated voltage: 380V±15%;

2.Rated frequency: 50Hz±2%;

3.Response time: full response time ≤5ms, instantaneous response time ≤100μs;

4.Compensation method: linear compensation;

5.Total harmonic compensation rate: ≥ 97%, 3/5/7/9 equal division independent compensation rate ≥ 98%;

6.Compensation effect: ≥0.99, can compensate capacitive and inductive reactive power;

7.Own loss: ≤2%;

8.Efficiency: ≥98%;

9.Working temperature: -10℃~+45℃;

10.Storage temperature: -25℃~+60℃;

11.Altitude: ≤1000m, above 1000m, use GB/T 3859.2 derating;

12.Relative humidity: 5%-95%, no condensation;

13.Overload protection: automatically limited to the rated current output;

14.Working mode: automatic or manual;

15.Communication interface: RS485, Ethernet, and communication functions are optional;

16.Module capacity: 30Kvar, 50Kvar, 75Kvar, 100Kvar, the same model can be directly paralleled;

17.Noise: ≤65dB;

18.Protection level: IP20;

19.Average switching frequency: 20KHz;

20.Cooling method: forced air cooling. 